How does the hybrid solar system calculator work?
The calculator solves three connected sizing problems — the PV array, the battery bank, and the hybrid inverter — from your daily energy use, local sun resource, and how much load you want backed up during an outage.
Enter use, sun & offset
Set your daily home energy use, local peak sun hours, and what share of your bill you want solar to cover.
Set your backup needs
Choose the load you want kept running during an outage, for how many hours, and your battery chemistry.
View your system sizes
See the PV array, battery, and inverter sizes, plus annual output, self-consumption, and export.
Why a hybrid system is sized in three connected steps
A grid-tied hybrid system has to satisfy three separate jobs at once, and each one drives a different component. The PV array is sized to hit your annual bill-offset target, using your daily use, local sun hours, and a performance ratio that accounts for real-world losses. The battery is sized independently, from the load you want backed up and for how long — it doesn't need to be big enough to store a whole day of solar production, only enough to ride out the outage duration you actually care about. The hybrid inverter then has to be rated for whichever of those two is larger, since it's the single component that both converts the array's DC output and powers your backed-up circuits.
Battery usable (kWh) = backed-up load × backup duration. Nameplate = usable ÷ (depth of discharge × round-trip efficiency). Inverter (kW) = larger of the array size or backed-up load, ×1.05 headroom.
Worked example: a full-offset home with a half-day of backup
30 kWh/day, 4.5 peak sun hours, 100% bill offset, lithium battery backing up 5 kW for 6 hours
Say your home uses 30 kWh a day, your area averages 4.5 peak sun hours, and you want solar to fully offset your annual bill. You want a lithium battery that can carry your fridge, well pump, and some outlets — a 5 kW backed-up load — for 6 hours during an outage, and you're using the default 80% performance ratio, 90% depth of discharge, and 95% round-trip efficiency.
- PV array: (30 kWh × 100%) ÷ (4.5 h × 0.80) = 30 ÷ 3.6 ≈ 8.3 kW.
- Battery usable: 5 kW × 6 h = 30 kWh.
- Battery nameplate: 30 ÷ (0.90 × 0.95) ≈ 35.1 kWh.
- Hybrid inverter: larger of 8.3 kW and 5 kW, ×1.05 ≈ 8.8 kW.
- Annual PV output: 8.3 kW × 4.5 h × 365 × 0.80 ≈ 10,950 kWh.
With 30 kWh of usable battery matching a full day's use, self-consumption lands around 95% — most of what the array produces gets used on-site rather than exported, leaving about 548 kWh exported to the grid over the year.
Result: about an 8.3 kW array, a 35.1 kWh lithium battery (30 kWh usable), an 8.8 kW hybrid inverter, and roughly 10,950 kWh of annual production at 95% self-consumption.
Worked example: a smaller array with lead-acid storage
20 kWh/day, 5.5 peak sun hours, 120% bill offset, AGM battery backing up 3 kW for 10 hours
Now suppose a smaller household uses 20 kWh a day in a sunnier location averaging 5.5 peak sun hours, and wants a 120% bill offset to leave room for an EV purchase next year. They're backing up a lighter 3 kW load — enough for a fridge and lighting — for a longer 10-hour outage, using an existing AGM lead-acid bank at 50% depth of discharge and 85% round-trip efficiency, with a 78% performance ratio for an older inverter.
- PV array: (20 kWh × 120%) ÷ (5.5 h × 0.78) = 24 ÷ 4.29 ≈ 5.6 kW.
- Battery usable: 3 kW × 10 h = 30 kWh.
- Battery nameplate: 30 ÷ (0.50 × 0.85) ≈ 70.6 kWh — more than double Example 1's, for the same usable energy, because lead-acid tolerates far less depth of discharge.
- Hybrid inverter: larger of 5.6 kW and 3 kW, ×1.05 ≈ 5.9 kW.
- Annual PV output: 20 kWh × 120% × 365 ≈ 8,760 kWh.
Result: about a 5.6 kW array, a 70.6 kWh AGM battery (30 kWh usable), a 5.9 kW hybrid inverter, and roughly 8,760 kWh of annual production at 90% self-consumption.
Understanding each result
PV array (kW DC) is the panel nameplate capacity needed to hit your bill-offset target, given your sun hours and performance ratio.
Battery nameplate and usable (kWh) separate what's printed on the battery from what you can actually draw. Usable capacity is driven purely by your backup load and duration; nameplate scales that up based on your chemistry's depth-of-discharge limit and round-trip efficiency.
Hybrid inverter (kW) is the continuous AC rating needed to handle the larger of your array's output or your backed-up load, with headroom so it isn't running at its ceiling.
Annual PV output (kWh) is what the sized array is expected to generate over a year — by construction, this tracks your daily use and bill-offset target directly, since that's exactly what the array was sized to hit.
Self-consumption (%) and annual grid export (kWh) describe how that output gets used. A battery sized to cover a meaningful share of your daily use shifts more midday solar surplus into evening use instead of exporting it, which is why self-consumption rises with battery size relative to daily use, up to a realistic ceiling.
Why annual output depends only on daily use and bill offset
You might notice the annual PV output figure doesn't change if you adjust sun hours or performance ratio on their own — only if you change your daily use or offset target. That's not a coincidence: this calculator first sizes the array specifically to hit your chosen offset target given those same sun-hour and performance-ratio assumptions, so they cancel out of the annual-output figure by construction. A lower performance ratio or fewer sun hours produces a physically larger array, not a smaller annual output — the array simply needs more panels to deliver the same energy target under weaker conditions.
Sizing the battery for backup, not for storage
It's a common assumption that a hybrid battery should store a full day of solar production, but that's usually oversized and expensive for what most homeowners actually want. This calculator instead sizes the battery for a specific backup scenario — a chosen load, for a chosen number of hours — which is typically a fraction of total daily use. If you want the battery to also meaningfully raise your self-consumption rate, increase the backed-up load or duration so its usable capacity approaches your full daily use, as in Example 1 above.
Common ways to use this calculator
Get a starting PV, battery, and inverter size before requesting quotes from installers.
Switch between lithium, AGM, and flooded to see how nameplate capacity and cost scale with depth of discharge.
Adjust backed-up load and duration to see the battery cost of backing up more or less of your home.
Set a bill offset above 100% to leave headroom for an EV or home addition.
Privacy and appropriate use
Your inputs are processed directly in your browser and are not sent to a database. This is a planning-stage estimate for component sizing, not an engineering, permitting, or utility-interconnection document — have a licensed solar installer verify final equipment selection, wiring, and code compliance for your specific site.