How does the solar fuse size calculator work?
The calculator applies the NEC 690.9 sizing rule that matches your circuit — 156% of Isc on the PV source side, 125% of continuous current everywhere else — then rounds up to the next standard fuse rating.
Pick the circuit type
PV string, battery→inverter, inverter DC input, or charge controller output — the sizing factor depends on which one.
Enter the current
Module Isc for a PV string, or the circuit's continuous current for everything else.
Get your fuse size
See the required minimum rating and the next standard fuse size to buy.
Why 1.56× for PV strings — the math behind NEC 690.9(B)
Two separate de-rating factors stack on the DC source side of a solar array. The first is the standard 125% continuous-duty factor: NEC defines a continuous load as one running three hours or more, and a PV array on a sunny day clearly qualifies, so every continuous-duty circuit needs an overcurrent device rated at 125% of the load. The second is a PV-specific 125% irradiance-enhancement factor, because cloud-edge effects and high-altitude irradiance can push a module's effective Isc 20–25% above its STC nameplate rating. Multiply the two together — 1.25 × 1.25 = 1.5625 — and NEC rounds that to the 156% figure in 690.9(B). Only the PV source side carries both factors; battery, inverter, and load-side circuits use the single 125% continuous-duty factor.
Round the result up to the next standard fuse rating — never down. Standard sizes: 1, 2, 3, 5, 6, 8, 10, 12, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A and up (NEC 240.6 / IEC 60269).
Worked example: a PV string fuse
Module Isc = 11.2 A, 2 modules in series, 3 strings in parallel
Three strings in parallel means per-string fusing is required under NEC 690.9(A), since a fault in one string could otherwise be back-fed by the other two.
- Required fuse: 11.2 A × 1.56 = 17.47 A.
- Round up: next standard size is 20 A.
Result: a 20 A gPV fuse rated at 1000 V DC or higher, one per string, in the combiner box.
Worked example: battery to inverter
48 V battery bank, 5,000 W continuous inverter, 92% efficiency
This is the circuit that carries the most fault current in a typical off-grid or hybrid system, which is why it gets a Class T fuse rather than a slower-blow type.
- Continuous DC current: 5,000 W ÷ (48 V × 0.92) ≈ 113 A.
- Required fuse: 113 A × 1.25 ≈ 141 A.
- Round up: next standard size is 150 A.
Result: a 150 A Class T fuse, mounted within 18 inches of the battery's positive terminal per NEC 706.30(C).
Where each fuse goes in a typical system
A typical DIY off-grid or hybrid solar system has three or four distinct fused DC circuits, each protecting a different cable run. The PV combiner fuses each string individually, but only matters once you have three or more strings in parallel — with one or two, cable ampacity alone usually protects the run. The PV array to charge controller run is fused at 1.56× the combined array current. The charge controller to battery run is fused at 1.25× the controller's rated continuous output. And battery to inverter — almost always the largest fuse in the system — is sized at 1.25× the inverter's continuous DC input current.
Every fuse also needs a DC voltage rating that covers the open-circuit voltage of its circuit: PV-side fuses typically need to handle up to 1000 V DC for residential arrays (1500 V DC for commercial), while battery-side fuses on a 48 V system need at least an 80 V DC rating with adequate interrupt capacity — Class T's 20,000 A interrupt rating is the typical choice.
Picking the fuse family: gPV vs. Class T vs. ANL
The amperage this calculator gives you is only half the spec — you still need to pick a fuse family suited to the circuit's voltage and prospective fault current. gPV fuses (IEC 60269-6) are purpose-built for PV strings at 1000–1500 V DC with fast clearing and low pre-arcing energy — the standard choice inside a combiner box. Class T fuses (UL 248-15) have very high interrupting capacity, around 20,000 A at 160 V DC, and are the standard for battery-to-inverter circuits, where a 12/24/48 V lithium or lead-acid bank can deliver enormous fault current. ANL, MIDI, and MEGA fuses are slower-blow with a lower interrupt rating — acceptable for DC loads under 32 V with moderate fault current, common in RV and marine systems, but not a substitute for Class T on a large lithium battery bank.
You never round down
When the calculation lands on a fractional value like 17.47 A, always round up to the next standard listed size. Rounding down means the fuse can nuisance-trip under completely normal operating current — that's both a reliability problem and a NEC violation, not a conservative safety margin. Always confirm your final selection against the equipment manufacturer's maximum overcurrent device rating too, printed on the module sticker, inverter spec sheet, or charge controller manual — the lower of the code calculation and the manufacturer spec wins.
Common ways to use this calculator
Get the right gPV fuse rating for each string before ordering parts.
Size the Class T fuse between your battery and inverter to the correct interrupt-rated amperage.
Verify a fuse someone else installed actually meets the 1.25×/1.56× minimum.
Work through PV, charge-controller, and inverter circuits one at a time before you buy fuses.
When to call a licensed electrician
Small RV and off-grid systems under 48 V DC, single-string roof installs, and prefab plug-and-play kits are reasonable DIY territory. Anything tying into the utility grid, run through conduit penetrating a roof or wall, operating at 1000+ V DC, using a lithium battery bank above 5 kWh, or installed in a jurisdiction that requires permits or inspections — which is most U.S. states — is licensed-electrician territory. This calculator gives you the correct fuse size; final installation still has to satisfy your local Authority Having Jurisdiction, and any grid-tied work needs a licensed electrician's sign-off.
Privacy and appropriate use
Your inputs are processed directly in your browser and are not sent to a database. This tool applies NEC 690.9 and 706.30 sizing rules for North American installations — international readers should note that IEC 60364-7-712, AS/NZS 5033, and CSA C22.1 use the same 1.56× factor for PV strings but may stock a different standard fuse size list for your market. This is a planning-stage reference, not a substitute for a licensed electrician or your local code authority.